TeSys D contactor
- 3P(3 NO)
- AC-3
- <= 440 V 32 A
- 24 V AC coil
Taxa Timbru Verde
este inclusa in pretul produsului
| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys D
|
|
| product or component type |
Contactor
|
|
| device short name |
LC1D
|
|
| contactor application |
Motor control
Resistive load |
|
| utilisation category |
AC-1
AC-3 AC-4 |
|
| poles description |
3P
|
|
| power pole contact composition |
3 NO
|
|
| [Ue] rated operational voltage |
<= 300 V DC for power circuit
<= 690 V AC 25...400 Hz for power circuit |
|
| [Ie] rated operational current |
32 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
50 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit |
|
| motor power kW |
15 kW at 380...400 V AC 50/60 Hz AC-3
7.5 kW at 220...230 V AC 50/60 Hz AC-3 18.5 kW at 500 V AC 50/60 Hz AC-3 18.5 kW at 660...690 V AC 50/60 Hz AC-3 15 kW at 415...440 V AC 50/60 Hz AC-3 7.5 kW at 400 V AC 50/60 Hz AC-4 |
|
| motor power HP (UL / CSA) |
2 hp at 115 V AC 50/60 Hz for 1 phase motors
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors 20 hp at 460/480 V AC 50/60 Hz for 3 phases motors 30 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
|
| control circuit type |
AC 50/60 Hz
|
|
| [Uc] control circuit voltage |
24 V AC 50/60 Hz
|
|
| auxiliary contact composition |
1 NO + 1 NC
|
|
| [Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947
|
|
| overvoltage category |
III
|
|
| [Ith] conventional free air thermal current |
50 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit |
|
| Irms rated making capacity |
550 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
|
| rated breaking capacity |
550 A at 440 V for power circuit conforming to IEC 60947
|
|
| [Icw] rated short-time withstand current |
138 A <= 40 °C 1 min power circuit
260 A <= 40 °C 10 s power circuit 430 A <= 40 °C 1 s power circuit 60 A <= 40 °C 10 min power circuit 100 A 1 s signalling circuit 120 A 500 ms signalling circuit 140 A 100 ms signalling circuit |
|
| associated fuse rating |
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1 |
|
| average impedance |
2 mOhm at 50 Hz - Ith 50 A for power circuit
|